The Kilargo KP2004 is a rigid, PVC-encased intumescent fire seal rebated into the perimeter of fire door assemblies. In a fire the sodium-silicate core expands to many times its volume, sealing the door perimeter against flames, hot smoke and toxic gases fully tested to AS 1530.4 for up to 2 hours on proprietary fire doors.

20mm x 4mmRigid PVC casingSelf-adhesiveFire rated 2hr30+ yr track record

Key Features

Proven product family with over 30 years in service historyHigh-performance sodium-silicate intumescent coreDecorative, protective rigid flame-retardant PVC outer casingRebated into the door or frame sits flush, protected for longevity in serviceAggressive self-adhesive tape backing no screwsGap size 13mm; black or grey (white & dark brown to special order)Ideal for fire-engineered solutions where extra protection is necessary; Australian made

What It’s Used For

Specify the KP2004 for machined-groove fire sealing in new fire doors and frames door manufacturers and frame fabricators rebate it flush into the edge, where the PVC casing protects the core from knocks and paint for the life of the door.

Use with a Kilargo medium-temperature smoke seal (IS1212, IS1515 or IS0511) to maintain tenable conditions across all smoke temperatures in a fully developed fire scenario.

Specifications

Type Rigid PVC-encased intumescent fire seal
Section 20mm x 4mm
Core Sodium-silicate based intumescent
Gap size Min. 1mm / max. 3mm (sits flush with door/frame edge)
Colours Black or grey (white & dark brown special order)
Available sizes 1000mm, 2100mm, 2400mm, 2700mm, 3000mm
Available finishes Black, Grey
MPN KP2004

Compliance & What It Means

Fire rated AS 1530.4 / AS 1905.1 (up to 2 hours). Fully tested to AS 1530.4 for up to 2 hours on proprietary fire door assemblies in accordance with AS 1905.1. In a fire, the intumescent core expands to many times its size and seals the gap, blocking flames, heat and hot toxic gases keeping the door assembly’s fire rating intact.

Fire and smoke approvals apply to tested, proprietary door assemblies. Always confirm suitability for your specific door type and required rating with your fire door manufacturer or building certifier.

Ordering & dispatch. This is a non-stocked, specialty architectural item ordered directly from the Kilargo factory line. Please allow a standard handling time of 58 business days after cleared payment before dispatch. Need it sooner, or not sure which seal suits your door? Call Prime Hardware on 1800 329 028.